FT/FIT-1001 Overview


FT & FIT-1001 Series are analog two wire flow transducers with a square root extractor, scaling multiplier, and output filter complete in a single package. The 4-20 mA output of the transducers is linear to velocity or volume. Each transducer is factory spanned and calibrated to meet the design requirement of the application and flow measuring elements being served. Optional features include local indication of the measured process air velocity and/or volume on either a 0.5 inch high 3-1/2 digit LCD display meter scaled in cfm (Model FIT-1001-D) and a built-in three-way manual zeroing valve for ease of zero verification and calibration (Models FT-1001-ZV, FIT-1001-DZV).

SpecificationsFT-1001FIT-1001-D
Accuracy±1.00% Full Scale
±0.5% Full Scale (Optional)
±1.00% Full Scale
±0.5% Full Scale (Optional)
DisplayNone
LCD
EnclosureFR110 PolycarbonateFlame retardant ABS plastic
Supply Power12-36 VDC18-36 VDC
Output4-20mA (2 Wire)4-20mA (2 Wire)
Temperature LimitsOperating 32°F-140°F
Storage -40°F-160°F
Operating 32°F-140°F
Storage -40°F-160°F
Zeroing ValveNone (Standard)
Manual Zeroing Valve (Optional)
None (Standard)
Manual Zeroing Valve (Optional)

FT/FIT-1003 Overview

FT & FIT-1003 Series are analog three wire flow transducers with a square root extractor, scaling multiplier, and output filter complete in a single package. The 0-5 or 0-10 VDC output of the transducers is linear to velocity or volume. Each transducer is factory spanned and calibrated to meet the design requirement of the application and flow measuring elements being served. Optional features include local indication of the measured process air velocity and/or volume on either a 0.5 inch high 3-1/2 digit LCD display meter scaled in cfm (Model FIT-1003-D)  and a built-in three-way manual zeroing valve for ease of zero verification and calibration (Models FT-1003-ZV, FIT-1003-DZV).

SpecificationsFT-1003FIT-1003-D
Accuracy±1.00% Full Scale
±0.5% Full Scale (Optional)
±1.00% Full Scale
±0.5% Full Scale
DisplayNone (Standard)LCD
EnclosureFR110 PolycarbonateFlame Retardant ABS Plastic
Supply Power12-36 VDC18-36 VDC
Output0-5 VDC (Standard)
0-10 VDC (Optional)
0-5 VDC (Standard)
0-10 VDC (Optional)
Temperature LimitsOperating 32°F-140°F
Storage -40°F-160°F
Operating 32°F-140°F
Storage -40°F-160°F
Zeroing ValveNone (Standard)
Manual Zeroing Valve (Optional)
None (Standard)
Manual Zeroing Valve (Optional)

FT/FIT-1005 Overview

FT & FIT-1005 Series are analog four wire flow transducers with a square root extractor, scaling multiplier, and output filter complete in a single package. The 4-20 mA, 0-5 VDC, or 0-10 VDC selectable output of the transducers is linear to velocity or volume. Each transducer is factory spanned and calibrated to meet the design requirement of the application and flow measuring elements being served. 

SpecificationsFT-1005
Accuracy±0.50% Full Scale
±0.25% Full Scale (Optional)
DisplayNone
EnclosureNEMA 12, Steel
NEMA 4, Steel (Optional)
Supply Power18-28 VDC
Output4-20mA or 0-10 VDC
0-5v (Optional)
Temperature LimitsOperating 32°F-160°F
Storage -40°F-180°F