FE-1500 Overview
The FE-1500 and FE-1500-FX airflow measuring stations consist of single or multiple airflow elements, factory mounted and pre-piped in a casing designed for flanged connection to the ductwork. The factory tested and packaged systems prevents installation errors associated with loose probes and installs similar to a control damper. The averaging Fechheimer design of the primary elements allows for ±20° of angular flow; decreasing the straight duct lengths required for installation. The FE-1500-FX model is equipped with a honeycomb airflow straightener for applications where flow may be especially turbulent. The FE-1500 and FE-1500-FX are accurate to ±2% of actual flow when installed according to the published guidelines. As a factory with full sheet metal capability, Paragon Controls can adapt the FE-1500 and FE-1500-FX to meet almost any application with fully customizable depths, flanges, and bell mouth fittings. Standard materials consist of a G90 galvanized casing and 6063-T5 anodized aluminum flow sensors, suitable for most HVAC applications; other application specific materials are available. Flow transducers are sold separately.
| Specifications | FE-1500 | FE-1500-FX |
|---|---|---|
| Accuracy | Within 2% of Actual Flow | Within 2% of Actual Flow |
| Operating Velocity Range | 100-10,000 fpm | 100-10,000 fpm |
| Temperature Limits | Galvanized & Aluminum 350ºF Continuous 400ºF Intermittent Stainless Steel Type 316L: 1600ºF Continuous/Intermittent | Galvanized & Aluminum 350ºF Continuous 400ºF Intermittent Stainless Steel Type 316L: 1600ºF Continuous/Intermittent |
| Humidity Limits | 0-100% Non-Condensing | 0-100% Non-Condensing |
| Instrument Connections | Aluminum 1/4" Compression Stainless Steel 1/8-27 Female NPT | Aluminum 1/4" Compression Stainless Steel 1/8-27 Female NPT |

FE1500 Series
Airflow Monitoring Stations
The FE-1500 and FE-1500-FX airflow measuring stations consist of single or multiple airflow elements, factory mounted and pre-piped in a casing designed for flanged connection to the ductwork. The factory tested and packaged systems prevents installation errors associated with loose probes and installs similar to a control damper.